Telekom DataCenter is located in the area Bratislava, Slovakia (Slovak Republic), and the colocation data center is carrier neutral. The data center was last updated on 11-05-2012.
The newest and largest datacenter of Slovak Telekom - Telekom DataCenter offers state-of-art technology fullfilling all needed standards that will provide secure and reliable platform for customer's systems.
Locality: - Bratislava, Varsavsk?24/A, capital of Slovak republic, (80 km fromd Vienna/Austria, 200 km from Budapest/Hungary, 130 km from Brno/Czech republic, 330 km from Prague/Czech republic) - Near to headquaters of all major headquaters of slovak companies and Slovak brach offices of international companies - Outside 100-year flood zone - Locality with low probability of seizmic activity - DC area separated and secured by fence and controlled by 24x7 security personnel located in DC
Building: - Detached building designed solely for the purposes of a data center - Own property with controlled entry to the grounds and buildings protected by a fence - Number of Floors: 1 underground floor + 4 floors - Building construction:poured concrete skeleton - Wheelchair transport route - external loading platform, doors dimensions 125/225cm - Freight elevator with loading capacity 3000 kg - Structurally separated part of IT Technology Hall - strict observance of zoning principle - all components of support technology (UPS, distributors, CRAC units, ...) outside IT rooms - Service and office space - parking spaces, preparation room, meeting room, office space for administrators, handy store room safes etc. - financed via own financial sources of Slovak Telekom without loans and application of building lien. Elimination of risk of change of DC owner/provider that can negatively affect quality of provided services
Electricity supply: - Connected to grid from two independent lines of HV connection involved in the loop - Transformers in redundacy n +1 - UPS in N+1redundancy, expandable to 2(N+1) without outage of DC, UPS capacity = 16 minutes in case of fully loaded DC - Diesel generators in N+1 redundancy - Total capacity of fuel for 48 hours operation in case of fully loaded DC refillable under operation - Maintenance of fuel tank without interruption of back-up capability (2 separate fuel tanks, redundant fuel pumps) - Fuel availability guaranteed also under special situation (e.g. gas crisis) due to the status of strategic company of Slovak republic - Distributed solution of power distributors of DC, elimination of typical critical point in datacenters - Both active paths of power supply A, B are designed for transfer of 100 % capacity also in case of major fault on one path - Fully redundant power distribution paths traced in separated fire zones - Power distribution via busbars - Power distributors for each IT room are located outside IT room and in separated fire zone for path A and path B
Cooling: - Hot and cold cooling system through the elevated floor - Internal cooling units for the IT room in n +2 redundancy - Chillers in N+1 redundancy, each chiller placed in separated fire zone with controlled access - Redundant cooling distribution paths: - circuit between chillers and cooling unit for IT rooms - tripled pipes - circuit between chillers and dry cooler - doubled pipes - Full redundancy of power feeding for active elements of cooling - Green technology "free cooling" - Preparation for the placement of water-cooled (high density) racks
IT halls: - 1200 m2 divided over three floors - Double floor height 100 cm - 5A flooring category - maximum score of 5 kN load floor (730kg/m2) - Headroom in IT rooms 300 cm - Assistive technology components (UPS, electrosplitters, refrigeration units, etc. ) outside of - IT halls - IT halls temperature conditions: 22 to 24 °C at a relative humidity of 40 to 60 % - Energy efficiency - in the long run will achieve PUE 1.5
Connectivity: - Connection to virtual private network of Slovak Telekom (IP/MPLS, Metro Ethernet, SDH, xWDM, ...) - Physical connection via two fully redundant optical paths entering into building through two separated entrances - Datacenter is directly incorporated to backbone network of Slovak Telekom (actually 2x10 Gbps with unlimited options for expansion) - Possibility to connect to other alternative providers (national or international) - Fully redundant high speed connection to Internet (interconnection to 5 international providersand highest capacity of interconnection to national Internet).
Monitoring and security: - Strict zoning principle: - High physical security and protection of IT technology - Avoidance of access of maintenance personnel to IT rooms - Access of maintenance personnel only to technology that they are responsible for e.g. person responsible for cooling has access to cooling technology, UPStechnician to UPS unit and so on. - Isolation of each redundant element of supporting technology to separated fire zone to minimalize damages and secure continuous DC operation also in case of fire - Continuous central monitoring of operational and critical conditions of supporting technologies, detection of increased temperature - Continuous monitoring of communication infrastructure - Access control system, electric security system, CCTV monitoring system - Early leak detection - Highly sensitive fire detection laser smoke detectors - Electronic fire alarm warning - Extinguishing equipment (gas HFC-227ea, covering an area within 10 seconds without damage to IT technology or bystanders) - 24 x 7 x 365 security guard
Services provided in DC: - Housing of IT technology - rental of highly secure space with guaranteed power supply and cooling - LAN services - interconnection of IT technology located in DC without necessity of installation and administration of own HW (router, switch) - Security - complex protection of IT technology via Firewall, IDS/IPS, Antispam, Antivirus based on robust, fully redundant solution from Fortinet - market leader in unified threat management (UTM) - "Remote access" and "remote hands" - secure remote access to IT technology or physical action of DC operator based on customer's request - DC relocation projects - complete coverage of relocation of IT technology, analysis, deinstallation/installation, testing, project management. - Archivation and back-up and restoration services - Consultancy, Analysis, Design in area of building or renewal of datacenters - Oursourcing a outtasking projects - Disaster Recovery / Business Continuity solutions - System and infrastructure integration / consolidation / virtualisation
For additional information/offer for DC services please contact us via tdc@telekom.sk