                                      Data Center Map

                                      Mobily Tier-2 Sulay


                                      » Index » Saudi Arabia » Riyadh » Mobily Tier-2 Sulay

                                      Mobily Tier-2 Sulay is located in the area Riyadh (ar-Riya?), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


                                      Address:
                                      Mobily
                                      Riyadh
                                      11423 Sulay
                                      Riyadh, Saudi Arabia

                                      » Request quote
                                      » Visit website

                                      Click here to find other data centers
                                      owned and operated by Mobily.


                                      Profile
                                      Tenants
                                      Connectivity
                                      Request quote
                                      Office space
                                      Rack Cabinets
                                      Dedicated Servers
                                      Suites
                                      Footprints
                                      Virtual Servers
                                      Cages
                                      Hosting of individual servers
                                      Remote Hands

                                      Profile


                                      MECHANICAL SYSTEM
                                      --------------------------

                                      a- Cooling System: Refrigerant cooling system.

                                      b- CRAH redundancy: N+1, Data Center equipment demand cooling load is 1000 W/m2

                                      c- Fuel Oil: Generator fuel oil storage 48 hours capacity

                                      d -BMS : Computerized Building Management System M&E equipment verification and management


                                      ELECTRICAL SYSTEM
                                      -------------------------
                                      a- Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.

                                      b- Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.

                                      c- Generators: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1

                                      d- Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel

                                      e- UPS: parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center

                                      f- Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time

                                      g- Security System : IP access control System and Analog CCTV system