  • Data Center Map

    Mobily Tier-2 Sulay


    » Index » Saudi Arabia » Riyadh » Mobily Tier-2 Sulay

    Mobily Tier-2 Sulay is located in the area Riyadh (ar-Riya?), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


    Address:
    Mobily
    Riyadh
    11423 Sulay
    Riyadh, Saudi Arabia

    » Request quote
    » Visit website

    Click here to find other data centers
    owned and operated by Mobily.


    Profile
    Tenants
    Connectivity
    Request quote
    Office space
    Rack Cabinets
    Dedicated Servers
    Suites
    Footprints
    Virtual Servers
    Cages
    Hosting of individual servers
    Remote Hands

    Profile


    MECHANICAL SYSTEM
    --------------------------

    a- Cooling System: Refrigerant cooling system.

    b- CRAH redundancy: N+1, Data Center equipment demand cooling load is 1000 W/m2

    c- Fuel Oil: Generator fuel oil storage 48 hours capacity

    d -BMS : Computerized Building Management System M&E equipment verification and management


    ELECTRICAL SYSTEM
    -------------------------
    a- Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.

    b- Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.

    c- Generators: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1

    d- Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel

    e- UPS: parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center

    f- Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time

    g- Security System : IP access control System and Analog CCTV system


    Mobily Tier-2 Sulay Pricing/Quotes


    If you are interested in receiving a quote for Mobily, please try our free quote service.

    Copyright © Data Center Map - Sitemap
    Your guide to colocation data centers, managed hosting, cloud servers etc.
    久久精品国产只有精品
  • <small id="ousky"></small><xmp id="ousky"><li id="ousky"></li>
  • <xmp id="ousky"><td id="ousky"></td><td id="ousky"></td><small id="ousky"><td id="ousky"></td></small>
  • <small id="ousky"><td id="ousky"></td></small>
  • <small id="ousky"><li id="ousky"></li></small>
  • <small id="ousky"><li id="ousky"></li></small>
  • <td id="ousky"></td>
  • <td id="ousky"></td><small id="ousky"></small>
  • <td id="ousky"></td>