                                      Mobily Tier-2 Malga 1 is located in the area Riyadh (ar-Riya?), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


                                      Address:
                                      Mobily
                                      Riyadh
                                      11423 Malga
                                      Saudi Arabia

                                      » Request quote
                                      » Visit website

                                      Click here to find other data centers
                                      owned and operated by Mobily.


                                      Profile
                                      Tenants
                                      Connectivity
                                      Request quote
                                      Office space
                                      Rack Cabinets
                                      Dedicated Servers
                                      Suites
                                      Footprints
                                      Virtual Servers
                                      Cages
                                      Hosting of individual servers
                                      Remote Hands

                                      Profile


                                      MECHANICAL SYSTEMS
                                      ---------------------------
                                      a-Cooling System: 11 x Air Cooled roof top Chillers.

                                      b- CRAH Redundancy: N+1, -CRAH demand cooling for data center is 1200w/m2.

                                      c-Fuel Oil: Generator fuel oil storage 48 hours capacity.

                                      d-BMS : Intelligent Building Management System M&E equipment verification and management.

                                      ELECTRICAL SYSTEMS
                                      --------------------------
                                      a-Design Load : 6 Mega Watt

                                      b-Transformers : 4 x 1.5 Mega VA

                                      c-Generators: 4 x3125 kVA 380/220v continuously rated diesel generators, design N+1 .

                                      d-UPS: parallel redundant system (N+N design) 200KVA modular units , 30 minute autonomy.

                                      e-Main Switch gear: 2 set of parallel switch gear for concurrently maintainable requirements.