                                      Mobily Tier-3 Jeddah


                                      » Index » Saudi Arabia » Jeddah » Mobily Tier-3 Jeddah

                                      Mobily Tier-3 Jeddah is located in the area Jeddah, Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


                                      Address:
                                      Mobily
                                      Jeddah
                                      5863 Fayah
                                      Saudi Arabia

                                      » Request quote
                                      » Visit website

                                      Click here to find other data centers
                                      owned and operated by Mobily.


                                      Profile
                                      Tenants
                                      Connectivity
                                      Request quote
                                      Office space
                                      Rack Cabinets
                                      Dedicated Servers
                                      Suites
                                      Footprints
                                      Virtual Servers
                                      Cages
                                      Hosting of individual servers
                                      Remote Hands

                                      Profile


                                      MECHANICAL SYSTEMS
                                      ---------------------------
                                      a-Cooling system Chilled water cooling system, dual flow and return with isolating valves at each T section.

                                      b- CRAH redundancy N+1, Data Center equipment demand cooling load is 1000 W/m2

                                      c-Fuel Oil Generator fuel oil storage 67 hours capacity at 100% load.

                                      d-BMS Computerized Building Management System M&E equipment verification and management.

                                      ELECTRICAL SYSTEMS
                                      ---------------------------
                                      a.Design load: The electrical connected load is 10.75 MVA with a demand load of 9 MVA.

                                      b-Transformers: 8 x 2500 kVA power transformer, 380/220V, 3P, 4W 60 Hz.

                                      c-Generators: 5 x 2000 kVA/1600 kW Continuous Rated Diesel Generators, Design in N+1.

                                      d-Paralleling Switch gear: Two set of paralleling switch gear for concurrently maintainable requirements monitored and controlled by two separate Load Shedding Panel.

                                      e- UPS: parallel redundant system in N+N configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center.

                                      f- Rectifier System Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

                                      g-Security System: IP access control system and IP CCTV integrated with BMS for On-Off Status only as per Security Department requirement.