Mobily Tier-3 Jeddah is located in the area Jeddah, Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.
MECHANICAL SYSTEMS --------------------------- a-Cooling system Chilled water cooling system, dual flow and return with isolating valves at each T section.
b- CRAH redundancy N+1, Data Center equipment demand cooling load is 1000 W/m2
d-BMS Computerized Building Management System M&E equipment verification and management.
ELECTRICAL SYSTEMS --------------------------- a.Design load: The electrical connected load is 10.75 MVA with a demand load of 9 MVA.
b-Transformers: 8 x 2500 kVA power transformer, 380/220V, 3P, 4W 60 Hz.
c-Generators: 5 x 2000 kVA/1600 kW Continuous Rated Diesel Generators, Design in N+1.
d-Paralleling Switch gear: Two set of paralleling switch gear for concurrently maintainable requirements monitored and controlled by two separate Load Shedding Panel.
e- UPS: parallel redundant system in N+N configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center.
f- Rectifier System Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.
g-Security System: IP access control system and IP CCTV integrated with BMS for On-Off Status only as per Security Department requirement.