  • Data Center Map

    Mobily Tier-3 Dammam


    » Index » Saudi Arabia » Dammam » Mobily Tier-3 Dammam

    Mobily Tier-3 Dammam is located in the area Dammam (Ad Dammam), Saudi Arabia (Kingdom of Saudi Arabia (KSA)), and the colocation data center is carrier neutral. The data center was last updated on 21-01-2014.


    Address:
    Mobily
    Dammam
    11423 Adama
    Dammam, Saudi Arabia

    » Request quote
    » Visit website

    Click here to find other data centers
    owned and operated by Mobily.


    Profile
    Tenants
    Connectivity
    Request quote
    Office space
    Rack Cabinets
    Dedicated Servers
    Suites
    Footprints
    Virtual Servers
    Cages
    Hosting of individual servers
    Remote Hands

    Profile


    MECHANICAL SYSTEMS
    ---------------------------
    a-Cooling system: Chilled water cooling system, dual flow and return with isolating valves at each T section.4 x. air cooled water chiller for Data Center, N+1

    b- CRAH redundancy N+1, Data Center equipment demand cooling load is 1000 W/m2.

    c-Fuel Oil: Generator fuel oil storage 67 hours capacity at 100% load

    D-BMS Computerized Building Management System M&E equipment verification and management

    ELECTRICAL SYSTEMS
    --------------------------
    a-Design load: The electrical connected load is 10.75 MVA with a demand load of 9 MVA.

    b-Transformers: 8 x 2500 kVA power transformer, 380/220V, 3P, 4W 60 Hz.

    c-Generators: 5 x 2000 kVA/1600 kW Rated Diesel Generators, Design in N+1.

    d-Paralleling Switch gear: Two set of paralleling switchgear for concurrently maintainable requirements monitored and controlled by two separate Load Shedding Panel.

    e-UPS: parallel redundant system in N+N configuration, 200 KVA modular units with 30 minute battery autonomy at full load.

    f-Rectifier System Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.

    g-Security System: IP access control system and IP CCTV integrated with BMS for On-Off Status only as per Security Department requirement.


    Mobily Tier-3 Dammam Pricing/Quotes


    If you are interested in receiving a quote for Mobily, please try our free quote service.

    Copyright © Data Center Map - Sitemap
    Your guide to colocation data centers, managed hosting, cloud servers etc.
    久久精品国产只有精品
  • <small id="ousky"></small><xmp id="ousky"><li id="ousky"></li>
  • <xmp id="ousky"><td id="ousky"></td><td id="ousky"></td><small id="ousky"><td id="ousky"></td></small>
  • <small id="ousky"><td id="ousky"></td></small>
  • <small id="ousky"><li id="ousky"></li></small>
  • <small id="ousky"><li id="ousky"></li></small>
  • <td id="ousky"></td>
  • <td id="ousky"></td><small id="ousky"></small>
  • <td id="ousky"></td>