                                      NEXT GENERATION DATA CENTRE
                                      544 RUE DE L'INSPECTEUR, MONTREAL

                                      COMPUTER ROOM SPECIFICATIONS
                                      Available rooms 7 dedicated data floors plus 1 half floor on ground level each with standard critical power of 1.5MW or 2.0MW per data floor, and high density ready.

                                      Typical data floors provide 10,000 SF for IT equipment, ~20,000 GSF, and cabinet space 600 standard 24'W x 48"D or 370 standard 32"W x 48"D per data floor. Standard power density of 150 watts per square foot with optional density of 200 watts per square foot

                                      Structural slab to slab floor heights are 16'6" with loading of over 200 pounds per square foot.

                                      19,140 SF of office available for lease and ~5,000 SF storage available in basement level

                                      7x24x365 Security with check points for all access, ballistic glass and walls, electronic access with dual authentication and minimum 1 biometric reader. Video surveillance 7x24x365 of all exterior and interior areas, and minimum 30 days of archive.

                                      CRITICAL POWER
                                      Total megawatts 30 MW

                                      UPS SYSTEMS
                                      Description - High efficiency static UPS
                                      Redundancy - N+1 or 2N as required

                                      GENERATORS
                                      Description - 2.75 MW diesel generator
                                      Redundancy - N+1 or 2N as required

                                      ON SITE FUEL CAPACITY
                                      5 x 50,000 L + 1 x 30,000 L underground diesel storage
                                      24 hours minimum run time

                                      HEAT REJECTION SYSTEMS
                                      Distributed and N+1 redundant KyotoCooling systems dedicated per data floor.
                                      Annualized PUE of 1.2 or better unaffected by critical load utilization.

                                      PDUs
                                      250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V
                                      secondary available. 2N redundancy.

                                      COMMUNICATIONS
                                      2 separate network points of entry with diverse underground duct banks to local network
                                      Dedicated diverse conduits and risers to each data floor.
                                      Carrier neutral facility with multiple carriers.

                                      FIRE PROTECTION
                                      Double interlocked pre-action dry type sprinkler system with VESDA throughout building

                                      DESIGN PUE
                                      Montreal NGDC is designed to be best in class with an annualized PUE of 1.20 or better regardless of critical load utilization